IDMT Relay Curves Explained

How inverse definite minimum time relay characteristics work, the standard IEC equation with a worked example, and how a relay test set verifies them.

CIE Instruments CIE Instruments
· · 6 min read

Over-current relays do not just trip at a set current. They trip after a time that depends on how large the current is, following a defined curve. These are the IDMT relays, short for Inverse Definite Minimum Time, and understanding their curves is essential for setting and testing protection. This guide explains the characteristic and how it is checked in practice.

Why Inverse Time

A larger fault should be cleared faster than a small overload, and the relay nearest the fault should operate before those upstream. An inverse characteristic gives exactly that: the higher the current, the shorter the trip time. A definite minimum time means the operating time stops falling at very high currents. Coordinating several relays in series depends on these shapes being predictable.

The Standard Equation

Standard curves follow the form: operating time t = TMS × k / ((I / Is)a − 1), where I is the fault current, Is is the plug setting (pick-up current), TMS is the time multiplier setting, and k and a are constants for the curve family. For the IEC standard inverse curve, k is 0.14 and a is 0.02.

IEC curve constants
Curve k a
Standard inverse 0.14 0.02
Very inverse 13.5 1
Extremely inverse 80 2

A Worked Example

Take a standard inverse relay with a plug setting of 100 A and a TMS of 0.5, and apply 400 A. The multiple is 400 / 100 = 4. Then 4 raised to the power 0.02 is about 1.028, so the denominator is about 0.028. The time is 0.5 × 0.14 / 0.028, which is roughly 2.5 seconds. Raise the current to 800 A and the multiple becomes 8, giving a denominator of about 0.0425 and a time of about 1.6 seconds. The relay really does trip faster as the current grows.

Check against the manufacturer's curve

Real relays have tolerances, and electromechanical relays differ from numerical ones. Always compare the measured time with the manufacturer's published curve and tolerance rather than only the formula.

How It Is Tested

A relay test set injects a controlled current into the relay's current input and measures the time it takes to trip, typically at several multiples of the plug setting, for example 2, 5 and 10 times. The measured times are compared with the curve, within the stated tolerance. The pick-up and drop-off current are also found by slowly raising and lowering the current. The built-in timer of a set like the CIE/RTS-5 measures trip time to a resolution of 1 ms.

Choosing a Relay Test Set

Single-phase sets cover over-current and earth fault relays, while directional and distance relays need three-phase sources with phase angle control. See the relay test sets and how to choose a relay test set. Duty cycle matters for high-current injection, so read duty cycle explained too. For the manual procedure, see how to test a relay.

Contact CIE for help matching a test set to your relays.

Cambridge Instruments & Engg. Co. · Est. 1963
Looking for an instrument,
not just an answer?
Multimeters, clamp meters, insulation testers, earth testers - manufactured in Howrah, India. Pan-India supply.