— Protection Testing · Relay Test Sets

RTS-33 Three-Phase Relay Test Set

Three-phase, two-unit relay test set — 0–360° phase angle, 0–50 A current, 415 V 3-phase input. For distance, directional, and differential relay testing.

RTS-33 — Three-Phase Relay Test Set

CIE® Guarantee

  • CIE® Registered Trade Mark
  • Calibrated Before Despatch
  • 12-Month Warranty
  • Made in India
  • Custom Ranges Available

About This Instrument

The CIE/RTS-33 is a three-phase relay test set for testing distance relays, over-current relays, over/under-voltage relays, earth fault relays, and directional-element relays. It is a two-unit system: Unit 1 houses the current/voltage source and measuring facilities; Unit 2 is the dedicated phase-shifter unit. Together they allow full 0–360° phase angle control between voltage and current (coarse 60° steps + fine ±30°), enabling genuine directional and distance relay testing not possible with single-phase sets. Three-phase input: 415 V ±10%, 4-wire, 50 Hz. Test current: 0–1/5/10/25/50 A (five taps, 0–100% regulation each). Continuous duty up to 10 A; 25 A and 50 A intermittent. Test voltage: 0–110% of 110 V phase-to-phase, three-phase, 50 Hz. Fixed DC voltage: isolated 30/110/220 V at 100 VA for 30 minutes. Phase-to-phase fault mode: selected phase currents automatically placed in opposition. Facility to check phase sequence before testing. Built-in digital timer (0–9.999 sec and 0–99.99 sec). Rated burden: 250 VA (current and voltage circuits). Units connected by 1-metre interconnection cable.

Technical Specifications

Specification Value
Input 415 V ±10%, 3 phase, 4 wire, 50 Hz A.C.
Burden 250 VA (current and voltage circuits)
Test Current Taps 0–1 A / 0–5 A / 0–10 A / 0–25 A / 0–50 A (0–100% regulation per tap)
Duty Continuous up to 10 A; 25 A & 50 A: intermittent (5 min ON, 10 min OFF)
Test Voltage 0–110% of 110 V ph-ph (63.5 V ph-N), 3-phase, 50 Hz, continuously variable
Fixed DC Voltage Isolated 30 V / 110 V / 220 V at 100 VA, available for 30 min
Phase Angle 0–360° — coarse 60° steps + fine ±30° (Unit 2, static phase-shifter)
Phase Angle Meter 360° range, 1° resolution
Time Measurement 0–9.999 sec (0.001 sec resolution) and 0–99.99 sec (0.01 sec resolution)
Current Metering CT-operated ammeter per phase, 0–1 A, 0–100% scaled, ±1% accuracy
Voltage Metering 0–200 V, ±1% accuracy, 0.1 V resolution, phase selector switch
Construction Two-unit system; 1-metre interconnection cable; 4-core, 5-metre mains input cable
Warranty 12 months against manufacturing defects

What's Included

  • Operation Manual
  • Schematic Circuit Diagram
  • Works Test Report
  • Guarantee Certificate
  • 1-metre interconnection cable (between Unit 1 and Unit 2)
  • 4-core, 5-metre mains input cable

Key Applications

  • Distance relay commissioning
  • Directional and differential protection relay testing
  • Over-current, earth fault, over/under-voltage relay testing
  • Phase-to-phase fault simulation
  • Indian Railways traction protection relay testing

12-Month Warranty · Direct After-Sales Support

Every CIE® instrument carries a 12-month warranty against manufacturing defects. After-sales support is handled directly by CIE — not a distributor network. Non-standard ranges or custom specifications can be manufactured to your requirement.

Interested in the RTS-33? Get a quote by email.

Email us with your model, quantity, and specification — we respond within one business day.