Free Engineering Tool

Insulation testing

Insulation Test Voltage Selector

Pick what you are testing and its rated voltage. Get the DC test voltage to set on your megger, and the band it falls in.

  • Free
  • No sign-up
  • Runs in your browser
  • Your numbers never leave your device

Inputs

What are you testing?
kV

Readout

SET-V DC
Embed this calculator on your website

Free to use on your blog, training page or company intranet. Paste this into any page that accepts HTML. The small credit link underneath is part of the deal.

Works on WordPress (Custom HTML block), Wix, Blogger and plain HTML. The calculator runs inside the frame and sends no data anywhere.

Rotating machines: IEEE 43-2013

IEEE 43 recommends a DC test voltage based on the winding's rated line voltage. Use the lower end for older or damp insulation, and the upper end for clean, dry, healthy windings.

Winding rated voltageTest voltage (DC)
Below 1000 V500 V
1000 to 2500 V500 to 1000 V
2501 to 5000 V1000 to 2500 V
5001 to 12000 V2500 to 5000 V
Above 12000 V5000 to 10000 V

Then judge the result with the Motor Minimum IR check and trend it with the PI and DAR calculator.

Low-voltage installations: IEC 60364-6

Circuit nominal voltageTest voltageMinimum IR
SELV and PELV250 V DC0.5 MΩ
Up to 500 V, including FELV500 V DC1.0 MΩ
Above 500 V up to 1000 V1000 V DC1.0 MΩ

Many national rules (including Indian practice and BS 7671) follow these values. Read the house wiring megger guide for the procedure.

Before you press the test button

  • Isolate and lock out the circuit, and confirm it is dead with a proper voltage tester.
  • Discharge the winding or cable after the test. Long cables and big windings store dangerous charge.
  • Your plant specification may call for a different voltage. Always follow the stricter document.