Power Factor Correction Calculator
Enter the load, your present power factor and the target. Get the capacitor kVAR to install and what it saves in kVA and current.
- Free
- No sign-up
- Runs in your browser
- Your numbers never leave your device
Inputs
kW
V
Supply
Readout
ADD-kVAR
kVA before
-kVA
kVA after
-kVA
kVA released
-kVA
Current before
-A
Current after
-A
Current saved
-%
Formula
kVARcap = kW × (tan φ₁ − tan φ₂) · φ = arccos(PF)
Example: 100 kW at 0.75 needs about 55.3 kVAR to reach 0.95. Line current falls in proportion to the power factor ratio, here by about 21%.
Practical notes
- Pick the nearest standard bank size at or just above the result, usually built from steps of 5, 10, 25 or 50 kVAR.
- Do not aim for unity. Over-correction under light load pushes a leading power factor and can raise the voltage. 0.95 to 0.98 is a sensible target.
- Capacitor output scales with voltage squared, so a capacitor rated at 440 V gives about 89% of its kVAR on a 415 V supply.
- Where there are many variable drives or rectifiers, harmonics can overload plain capacitors. Use detuned (reactor-fitted) banks and measure first.
To measure the present power factor and load, a clamp meter with power functions is the simplest tool. The three-phase power calculator converts between kW, kVA and amps.