Cable Voltage Drop Calculator
Enter the cable size, length and load current. See the voltage drop, how it compares with the usual limits, and the longest run that stays within them.
- Free
- No sign-up
- Runs in your browser
- Your numbers never leave your device
Inputs
Readout
Formulas
R = ρ(T) × L / A · ρ(T) = ρ₂₀ × (1 + α × (T − 20))
3-phase: ΔV = √3 × I × R · 1-phase: ΔV = 2 × I × R
Values used: copper ρ₂₀ = 0.01724 Ω·mm²/m with α = 0.00393 per °C, aluminium ρ₂₀ = 0.0282 Ω·mm²/m with α = 0.00403 per °C. For three-phase, enter the line-to-line voltage; for single-phase, the phase-to-neutral or two-wire supply voltage.
Typical limits
- Many Indian and international practices work to a total drop of about 3% for lighting and 5% overall from the supply point to the farthest load. Your own specification may differ.
- For a motor, also check the drop while it starts. The starting current is several times the running current, and a deep dip can stop it from starting.
What this estimate leaves out
- It counts conductor resistance only. For large cables, above about 50 mm², reactance adds to the drop, especially at low power factor, so the real figure is higher.
- It does not check the cable's current rating, grouping or derating, or short-circuit withstand. Use it alongside a proper cable sizing table.
To measure the actual drop, read the voltage at the source and at the load under load with a digital multimeter. The Ohm's law tool helps with the maths.