Reference

IP and CAT ratings explained

Two codes on almost every instrument datasheet. One says how well it survives dust and water, the other says where on the electrical system it is safe to measure.

IP code (IEC 60529)

Written as IP followed by two digits, for example IP54. The first digit is protection against solid objects and dust (0 to 6). The second is protection against water (0 to 9). An X replaces a digit that was not tested, as in IPX4. The rating IPX9K or IP69K, often seen on wash-down equipment, comes from DIN 40050-9 and ISO 20653 (road vehicles), not from the base IEC 60529 table.

First digit: solids and dust
DigitProtected against
0No protection
1Objects over 50 mm (back of a hand)
2Objects over 12.5 mm (a finger)
3Objects over 2.5 mm (tools, thick wire)
4Objects over 1 mm (thin wire)
5Dust protected (limited ingress, no harmful deposit)
6Dust tight (no ingress)
Second digit: water
DigitProtected against
0No protection
1Vertically dripping water
2Dripping water, enclosure tilted up to 15 degrees
3Spraying water, up to 60 degrees from vertical
4Splashing water from any direction
5Water jets (6.3 mm nozzle)
6Powerful water jets (12.5 mm nozzle)
7Temporary immersion, up to 1 m for 30 minutes
8Continuous immersion, to conditions the maker states
9High-pressure, high-temperature water jets (about 80 °C)

IP ratings describe the enclosure, not the whole instrument in use. A case that is rated closed may not be rated with the battery door open or a probe plugged in. See the IP rating guide.

CAT rating (IEC 61010-1)

The measurement category tells you how much energy sits behind the point you are measuring. The closer to the supply source, the higher the available fault current and the larger the transients, so the higher the category you need. A meter rated CAT III 600 V is built to survive the transients of that location at up to 600 V. It is not a CAT IV meter.

Measurement categories
CategoryLocationTypical examples
CAT IProtected electronic circuits and signal-level equipmentCircuits not directly connected to mains, or protected by limiting devices
CAT IISingle-phase receptacle-connected loadsAppliances, portable tools, socket outlets on long branch circuits
CAT IIIFixed installation, distribution levelDistribution boards, bus bars, feeders, motors on fixed wiring
CAT IVOrigin of the installationService entrance, meter, primary overcurrent protection, overhead and underground supply lines

Impulse withstand by category and rated voltage

Peak transient the instrument is designed to survive, for the common rated voltages.

Impulse withstand voltages
Rated voltageCAT IICAT IIICAT IV
300 V2.5 kV4 kV6 kV
600 V4 kV6 kV8 kV
1000 V6 kV8 kV12 kV

The category tests also differ in source impedance (lower for CAT III and IV than for CAT II), so a CAT II 1000 V meter is not equivalent to a CAT III 600 V meter even where both quote 6 kV. A higher voltage number does not make up for a lower category. CAT III 300 V withstands a smaller transient than CAT III 600 V, and CAT IV 300 V and CAT III 600 V both withstand 6 kV but are meant for different locations. Pick the category of the location first, then a voltage rating at or above the system voltage. Read the full CAT rating guide.

Tables summarise the published codes. Check the marking on your own instrument and the current edition of the standard before relying on any rating for safety.