Print it at 100 % on A4. Page 1 is the form you fill in. The next page is the worksheet and reference.
Need the instrument?
What is inside
- Equipment details: panel, rated current, conductor material, temperature, instrument and test current used
- Ten test lines with measured value, value corrected to 20 °C, baseline, change in percent, maximum allowed and result
- A phase comparison block with deviation from the lowest phase
- Formulas for copper and aluminium correction, change against baseline and joint heating (P = I²R), with worked examples
- Guide bands, common causes of a high reading and method notes on four-terminal connection and test current
How it was checked
Temperature corrections use the usual coefficients of 0.00393 for copper and 0.00403 for aluminium near 20 °C, and the worked example was checked. The deviation bands are commonly quoted practice, not limits from a standard. For circuit breaker contacts, standards usually call for a DC test current of 100 A or more, so check that your instrument is suitable for the item.