Print it at 100 % on A4. Page 1 is the form you fill in. The next page is the worksheet and reference.
Need the instrument?
What is inside
- Settings, CT ratio and the working to turn primary settings into secondary injection currents
- Pickup, drop-off, six timing points and the high-set element, each with expected, measured and result columns
- Tolerance boxes for you to fill from the relay datasheet. The form assumes none
- Base operating times at TMS = 1 for the standard, very, extremely and long-time inverse curves, so expected time = base × TMS
- An eight-item checklist, a sign-off block and a log-log plot sheet for expected against measured times
How it was checked
Base times are calculated from t = k / ((I / Is)^α - 1) and the formula was checked against independent calculations. The constants are from IEC 60255-151, so confirm your relay uses the same characteristic.