HV to LV, winding to earth, core to earth

Transformer Insulation Resistance (Megger) Report Format, Free PDF

The standard set of transformer megger tests on one page, with a worksheet that corrects each reading to 20 °C and calculates DAR and PI.

  • Free
  • No sign-up
  • A4, 2 pages
  • Formulas and limits included
Preview of the Transformer Insulation Resistance (Megger) Report form
Download the PDF formA4, 2 pages

Print it at 100 % on A4. Page 1 is the form you fill in. The next page is the worksheet and reference.

Need the instrument?

What is inside

  • Transformer details: make, rating, vector group, HV and LV voltage, oil and winding temperature, ambient and weather
  • Readings at 15 s, 60 s and 10 min for HV to LV and earth, LV to HV and earth, HV and LV to earth, HV to LV, tertiary and core to earth
  • Columns for the temperature factor, IR60 at 20 °C, DAR and PI, plus an evaluation table against your acceptance value
  • A temperature factor table from 10 to 80 °C, the formulas and a worked example
  • Guide values clearly marked as rules of thumb, and method notes on isolation, guard use and discharge

How it was checked

Temperature factors are calculated from K20 = 2^((T − 20) / 10), the usual halving per 10 °C rule referred to 20 °C. For oil-filled units the real slope can differ, so use the manufacturer or IEEE C57.152 table where you have one. The 1 MΩ per kV rule is a guide, not a standard limit.

Related

Common questions

Which tests make up a transformer megger test?

The usual set is HV to LV and earth, LV to HV and earth, HV and LV to earth, and sometimes HV to LV with the guard terminal used. Core to earth is also checked with the core earth link removed.

What test voltage do I use on a transformer?

It is commonly 5 kV DC for HV windings and 1 kV DC for LV windings, or 500 V for windings below 1 kV. Use the voltage your specification or the manufacturer gives.

Using the form

  • Limits and constants come from the standards named above, as commonly quoted. Check them against the edition you work to, and use the stricter of those and your specification.
  • Where a value is a common guide rather than a limit from a standard, the form says so.
  • This is a calculation aid for qualified people. It does not replace the standard, the instrument manual or your site safety procedure.