What is inside
- Nameplate and job details, winding material, connection and thermal class
- Timed insulation resistance for U, V, W and all windings to earth, with PI
- Winding resistance for U-V, V-W and W-U, corrected to 75 °C, with change against the factory or previous value and an imbalance box
- An optional no-load current and voltage table
- Page 2: copper and aluminium correction formulas, a correction factor table from 10 to 85 °C, and findings with likely causes
How it was checked
The R75 / RT factors are calculated from the formula shown (constants 235 for copper, 225 for aluminium) and the worked example was checked by hand. The 2 % imbalance, minimum IR and PI values and the no-load current range are rules of thumb marked as guides. Use the factory report, the standard or your site limit.