Print it at 100 % on A4. Page 1 is the form you fill in. The next page is the worksheet and reference.
Need the instrument?
What is inside
- Installation details, earthing system, test instrument and test voltage
- A 14-circuit table with live-live, live-earth and neutral-earth readings, the minimum and pass or fail for each
- A note on three-phase circuits and on disconnecting electronics before the test
- Page 2: test voltage and minimum IR by circuit voltage, a five-step method, and a table of what a low reading usually means
How it was checked
The test voltages (250 V, 500 V, 1000 V) and minimum values (0.5 and 1 MΩ) are as commonly quoted from IEC 60364-6 and are shown as guides. Local wiring rules or your supply company may ask for more, so use the strictest. The form has no calculations.